12. (M) Item and Output Signal for Monitoring
12.7 Output frequency detection
NOTE
• All signals are OFF during the DC injection brake operation and during tuning at start-up.
• The reference frequency in comparison with the set frequency differs depending on the control method.
• Setting a higher value in
Pr.870
causes a lower responsivity of the signals for frequency detection (SU, FB, and LS signals).
• The logic (ON/OFF switching) of the LS signal is the reverse of that of the FB signal.
• Changing the terminal assignment using
Pr.190 to Pr.196 (Output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)
Pr.874 OLT level setting
Control method or function
Reference frequency
FU
FB, SU, LS
V/F control
Output frequency
Output frequency
Advanced magnetic flux vector
control
Output frequency before the slip
compensation
Output frequency before the slip
compensation
Real sensorless vector control
Frequency command value
Estimated frequency (actual motor
speed)
Encoder feedback control
Frequency converted from actual
motor speed
Frequency converted from actual motor
speed
Vector control
Frequency command value
Frequency converted from actual motor
speed
PM sensorless vector control
Frequency command value
Estimated frequency (actual motor
speed)
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...