12. (M) Item and Output Signal for Monitoring
12.6 Output terminal function selection
• The Operation ready 2 (RY2) signal turns ON when the pre-excitation starts. The signal is ON during pre-excitation even
while the inverter is stopped. The signal is OFF during the inverter output shutoff.
NOTE
• When pre-excitation works with the Pre-excitation (LX) signal ON, the RY2 signal turns ON after 100 ms from the time the LX
signal turns ON. (When online auto tuning at start-up is selected (
Pr.95
= "1"), the time the signal turns ON is delayed by the
tuning time.)
• The ON/OFF state of each signal according to the inverter operating status is shown in the matrix below.
*1
When the start signal is ON and the frequency command is 0 Hz, such state is designated as "during zero speed control".
*2
The signal is OFF during power failure or undervoltage.
*3
The signal turns ON after 100 ms from the time the LX signal turns ON.
*4
This means the state during a fault occurrence or while the MRS signal is ON, etc.
*5
The signal is OFF while power is not supplied to the main circuit.
• To use the RY, RY2, RUN, RUN2, or RUN3 signal, set the corresponding number selected from the following table in any
of
Pr.190 to Pr.196 (Output terminal function selection)
to assign the function to an output terminal.
Time
Power
supply
STF
RH
RY
Reset
processing
ON
OFF
OFF
OFF
OFF
OFF
MRS
Pr. 13
RUN
RUN2
OFF
OFF
OFF
OFF
OFF
OFF
RUN3
OFF
Output frequency
ON
ON
ON
ON
ON
ON
ON
Pre-excitation
(zero speed control)
RY2
OFF
ON
100 ms
LX
RY2
ON
ON
Output
signal
Start
signal
OFF
(inverter
stopped)
Start signal
(durin
g pre-
excitation)
Start
signal
ON
(inverter
running)
LX signal
ON (during
pre-
excitation)
During DC
injection
brake
operation
(during pre-
excitation)
Inverter output
shutoff
Automatic restart after
instantaneous power failure
During coasting
Inverter
running
after
restart
Start
signal
ON
Start
signal
OFF
Start
signal
ON
Start
signal
OFF
RY
ON
ON
ON
ON
ON
OFF
ON
RY2
OFF
ON
ON
ON
OFF
OFF
ON
RUN
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
RUN2
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
RUN3
OFF
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
Output signal
Pr.190 to Pr.196 settings
Positive logic
Negative logic
RY
11
111
RY2
33
133
RUN
0
100
RUN2
44
144
RUN3
45
145
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...