13. (T) Multi-Function Input Terminal Parameters
13.7 Inverter output shutoff
Assigning a different action for each MRS signal input via
communication and external terminal (Pr.17 = "4 or 5")
• When
Pr.17
= "4 or 5", the MRS signal input from an external terminal is normally closed (NC contact), and the MRS signal
input from communication is normally open (NO contact). This function is useful to perform operation via communication
while keeping the ON state of the MRS signal input from the external terminal.
Operation when PU operation interlock enabled (Pr.79 = "7")
• When the X12 signal is not assigned to any input terminal while the PU operation interlock is enabled (
Pr.79
= "7"), the
MRS signal is used as the X12 signal. The logic for the MRS signal used as the X12 signal is changed by the
Pr.17
setting.
• The operation when the PU operation interlock is enabled (
Pr.79
= "7") is as follows.
NOTE
• When using an external terminal to input the MRS signal, the MRS signal shuts off the output in any of the operation modes.
• The MRS signal is valid regardless of whether it is input through the external terminal or via network (except for the FR-E800-
SCE), but when the MRS signal is used as the Inverter run enable (X10) signal, input the signal through the external terminal.
• When the terminal assignment is changed using
Pr.178 to Pr.189 (Input terminal function selection)
, wiring may be
mistaken due to different terminal name and signal contents, or may affect other functions. Set parameters after confirming
the function of each terminal.
Parameters referred to
Pr.79 Operation mode selection
Pr.178 to Pr.189 (Input terminal function selection)
External MRS
Communication MRS
Pr.17 setting
0, 1
2, 3
4, 5
OFF
OFF
Operation enabled
Output shutoff
Output shutoff
OFF
ON
Output shutoff
Output shutoff
Output shutoff
ON
OFF
Output shutoff
Output shutoff
Operation enabled
ON
ON
Output shutoff
Operation enabled
Output shutoff
Pr.17 setting
MRS signal
X12 signal
MRS function
X12 function
0, 1
Assigned
Not assigned
PU operation interlock (NO contact) —
Not assigned
Assigned
—
PU operation interlock (NO contact)
Assigned
Assigned
Output shutoff (NO contact)
2 to 5
Assigned
Not assigned
PU operation interlock (NC contact) —
Not assigned
Assigned
—
PU operation interlock (NO contact)
Assigned
Assigned
Output shutoff (NC contact)
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...