13. (T) Multi-Function Input Terminal Parameters
13.5 Torque (magnetic flux) setting current (voltage) bias and gain
Torque setting current (voltage) bias/gain adjustment method
Adjustment by applying current (voltage) between terminals 4 and 5 to set the current (voltage)
at the bias/gain torque
Operating procedure
1.
Turning ON the power of the inverter
The operation panel is in the monitor mode.
2.
Changing the operation mode
Press the PU/EXT key to choose the PU operation mode. The PU LED turns ON.
3.
Selecting the parameter setting mode
Press the MODE key to choose the parameter setting mode. (The parameter number read previously appears.)
4.
Calibration parameter selection
Turn the setting dial or press the UP/DOWN key until "C..." appears. Press the SET key to display "C---".
5.
Selecting a parameter
Turn the setting dial or press the UP/DOWN key until "C41" (
C41 (Pr.933) Terminal 4 gain (torque/magnetic flux)
)
appears.
6.
Displaying analog current (voltage) value
Press the SET key to display the analog current (voltage) value (%) currently applied to terminal 4.
Do not touch the setting dial and UP/DOWN key until calibration is completed.
7.
Applying current (voltage)
Apply a 20 mA (5 V). (Turn the external potentiometer connected between terminals 4 and 5 to a desired position.)
8.
Setting completed
Press the SET key to confirm the setting. The analog current (voltage) value (%) blinks when it is applied.
• Turn the setting dial or press the UP/DOWN key to read another parameter.
• Press the SET key to return to the "C---" display.
• Press the SET key twice to show the next parameter.
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...