193
8. (E) Environment Setting Parameters
8.18 Current average value monitor signal
1
2
3
4
5
6
7
8
9
10
NOTE
• Masking of the data output and sampling of the output current are not performed during acceleration/deceleration.
• If constant speed changes to acceleration or deceleration during start pulse output, it is judged as invalid data, and HIGH
output in 3.5 seconds intervals is performed for the start pulse and LOW output in 16.5 seconds intervals is performed for the
end signal. After the start pulse output is completed, minimum 1-cycle signal output is performed even if acceleration/
deceleration is performed.
• If the output current value (inverter output current monitor) is 0 A at the completion of the 1-cycle signal output, no signal is
output until the next constant-speed state.
• Under the following conditions, the Y93 signal is output with LOW output in 20 seconds intervals (no data output).
• Changing the terminal assignment using
Pr.190 to Pr.196 (Output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.57 Restart coasting time
,
Pr.190 to Pr.196 (Output terminal function selection)
Pr.503 Maintenance timer
End signal
Y93
signal
Start pulse
Invalid cycle (20 s)
Next cycle
Time
Output frequency
The speed is changed to deceleration from
the constant speed during start pulse output
Previous cycle
Output as high pulse shape for 3.5 s
Output as low pulse shape for 16.5 s
- When acceleration or deceleration is operating at the completion of the 1-cycle signal output
- When automatic restart after instantaneous power failure (
Pr.57 Restart coasting time
≠
"9999") is set, and the 1-
cycle signal output is completed during the restart operation.
- When automatic restart after instantaneous power failure (
Pr.57
≠
"9999") is set, and the restart operation was being
performed at the completion of data output masking.
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...