15. (A) Application Parameters
15.7 Automatic restart after instantaneous power failure / flying start with an induction motor
15.7
Automatic restart after instantaneous power failure
/ flying start with an induction motor
The inverter can be restarted without stopping the motor operation in the following situations:
• When an instantaneous power failure occurs during inverter running
• When the motor is coasting at start
*1
The coasting time when
Pr.57
= "0" is as shown below. (When
Pr.162
and
Pr.570
are set to the initial value.)
0.5 s for the FR-E860-0027(1.5K) or lower.
1 s for the FR-E820-0080(1.5K) or lower, FR-E840-0040(1.5K) or lower, FR-E860-0040(2.2K) or higher, and FR-E820S-0080(1.5K) or lower.
2 s for the FR-E820-0110(2.2K) or higher, FR-E840-0060(2.2K) or higher, and FR-E820S-0110(2.2K).
• To operate the inverter with the automatic restart after instantaneous power failure function enabled, check the following
points.
• Set
Pr.57 Restart coasting time
= "0".
Setting for the automatic restart after instantaneous power failure
operation (Pr.162)
• The
Pr.162
settings and the instantaneous power failure automatic restart operation under each operation mode are as
shown in the following table.
Pr.
Name
Initial
value
Setting
range
Description
162
A700
Automatic restart after
instantaneous power
failure selection
0
0
Frequency search only performed at the first start
1
Reduced voltage start only at the first start (no frequency search) or encoder
detection frequency search
10
Frequency search at every start
11
Reduced voltage start at every start (no frequency search) or encoder
detection frequency search
299
A701
Rotation direction
detection selection at
restarting
0
0
Rotation direction detection disabled
1
Rotation direction detection enabled
9999
When
Pr.78 Reverse rotation prevention selection
= "0", with rotation
direction detection
When
Pr.78 Reverse rotation prevention selection
= "1 or 2", without
rotation direction detection
57
A702
Restart coasting time
9999
0
Coasting time differs according to the inverter capacity.
0.1 to 30 s
Set the time delay for the inverter to perform a restart after restoring power
due to an instantaneous power failure.
9999
No restart
58
A703
Restart cushion time
1 s
0 to 60 s
Set the voltage cushion time for restart.
165
A710
Stall prevention operation
level for restart
150%
0% to 400%
Set the stall prevention level at restart operation on the assumption that the
inverter rated current is 100%.
611
F003
Acceleration time at a
restart
9999
0 to 3600 s
Set the acceleration time to reach
Pr.20 Acceleration/deceleration
reference frequency
at restart.
9999
Standard acceleration time (for example,
Pr.7
) is applied as the acceleration
time at restart.
Pr.162 setting
Restart
operation
V/F control,
Advanced magnetic flux vector control
Real sensorless
vector control
Vector control
Without encoder
With encoder
0 (initial value) At first start
Frequency search
Frequency search
Frequency search
Encoder detection
frequency search
1
At first start
Reduced voltage start
Encoder detection
frequency search
10
At every start
Frequency search
Frequency search
11
At every start
Reduced voltage start
Encoder detection
frequency search
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux Sensorless
Sensorless
Sensorless Vector
Vector
Vector
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...