15. (A) Application Parameters
15.5 Calibration of PID display
15.5
Calibration of PID display
When the operation panel or the parameter unit (FR-PU07) is used, the display unit of parameters and monitor items related
to PID control can be changed to various units.
*1
On the LCD operation panel or the parameter unit used as the command source, the parameter number in parentheses appears instead of that
starting with the letter C.
Calibration of PID display bias and gain (C42 (Pr.934) to C45 (Pr.935))
• When both
C42 (Pr.934) and C44 (Pr.935)
≠
"9999", the bias and gain values for the set point, measured value and
deviation in PID control can be calibrated.
• "Bias"/"gain" function can adjust the relation between PID displayed coefficient and measured value input signal that is
externally input. Examples of these measured value input signals are 0 to 5 VDC, 0 to 10 VDC, or 4 to 20 mADC. (The
terminals used for measured value input can be selected at
Pr.128, Pr.609, Pr.610
.)
• Set the value that is displayed when the PID measured value (control amount) is 0% to
C42 (Pr.934)
and the value that is
displayed when the PID measured value (control amount) is 100% to
C44 (Pr.935)
.
• When both
C42 (Pr.934) and C44 (Pr.935)
≠
"9999" and
Pr.133
is set as the set point, the setting of
C42 (Pr.934)
is treated
as 0%, and
C44 (Pr.935)
as 100%.
• There are three methods to adjust the PID display bias/gain.
for details, and make the necessary adjustments by considering
C7 (Pr.905)
as
C45 (Pr.935) and Pr.126
as
C44 (Pr.935)
.
Pr.
Name
Initial value
Setting
range
Description
759
A600
PID unit selection
0
0 to 43
Change the unit of the PID control-related values that is
displayed on the LCD operation panel (FR-LU08) or the
parameter unit (FR-PU07).
9999
Without display unit switching
C42 (934)
A630
PID display bias coefficient
9999
0 to 500
Set the coefficient of the bias side (minimum) of measured value
input.
9999
Displayed in %.
C43 (934)
A631
PID display bias analog value
20%
0% to 300%
Set the converted % of the bias side (minimum) current/voltage
of measured value input.
C44 (935)
A632
PID display gain coefficient
9999
0 to 500
Set the coefficient of the gain side (maximum) of measured value
input.
9999
Displayed in %.
C45 (935)
A633
PID display gain analog value
100%
0% to 300%
Set the converted % of the gain side (maximum) current/voltage
of measured value input.
100
0
0
0
0
Frequency setting signal
100%
20mA
5V
10V
C45(Pr.935)
Initial value
Bias
C42(Pr.934)
Gain
C44(Pr.935)
20
4
1
2
C43(Pr.934)
Coef
ficient
Method to adjust any point by application of a current (voltage) to the measured value input terminal
Method to adjust any point without application of a current (voltage) to the measured value input terminal
Method to adjust only the display coefficient without adjustment of current (voltage)
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...