15. (A) Application Parameters
15.7 Automatic restart after instantaneous power failure / flying start with an induction motor
Restart operation with frequency search (Pr.162 ="0 or 10", Pr.299)
• When
Pr.162
= "0 (initial value) or 10", the motor speed is detected at a power restoration so that the motor can re-start
smoothly.
• The encoder also detects the rotation direction so that the inverter can re-start smoothly even during the reverse rotation.
• Whether or not to detect the rotation direction can be selected by
Pr.299 Rotation direction detection selection at
restarting
. If the motor capacity is different from the inverter capacity, set
Pr.299
= "0" (no rotation direction detection).
• When the rotation direction is detected, the following operation is performed according to
Pr.78 Reverse rotation
prevention selection
setting.
○
: With rotation direction detection ×: Without rotation direction detection
NOTE
• The rotation speed detection time (frequency search) changes according to the rotation speed of the motor (maximum 1
second).
• When the inverter capacity is two ranks or greater than the motor capacity, the overcurrent protective function (E.OC[]) is
sometimes activated and prevents the inverter from restarting.
• If two or more motors are connected to one inverter, this function operates abnormally. (The inverter does not restart
successfully.)
• Because a DC injection brake is applied instantaneously at speed detection during a restart, the speed might drop if the
moment of inertia (J) of the load is small.
• If reverse operation is detected when "1" (reverse rotation disabled) is set to
Pr.78
, operation decelerates by reverse rotation
and then changes to forward rotation when the start command is forward rotation. The inverter does not restart when the start
command is reverse rotation.
Pr.299 setting
Pr.78 setting
0
1
2
9999
○
×
×
0 (initial value)
×
×
×
1
○
○
○
Instantaneous (power failure) time
Power supply
(R/L1, S/L2,
T/L3)
Motor speed N
(r/min)
Inverter output
frequency f(Hz)
Inverter output
voltage E(V)
Coasting
time (
Pr.57
)
Speed
detection
time
+
Acceleration time
at a restart
(
Pr.611
setting)
Restart cushion
time (
Pr.58
setting)
*
*
The output shut off timing differs
according to the load condition.
V/F control, Advanced magnetic flux vector control
Instantaneous (power failure) time
Power supply
(R/L1, S/L2,
T/L3)
Motor speed N
(r/min)
Inverter output
frequency f(Hz)
output voltage
E(V)
Coasting
time (
Pr.57
)
Speed
detection
time
+
Acceleration time
at a restart
(
Pr.611
setting)
*
Real sensorless vector control
*
The output shut off timing differs
according to the load condition.
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...