8. (E) Environment Setting Parameters
8.15 PWM carrier frequency and Soft-PWM control
1
2
3
4
5
6
7
8
9
10
NOTE
• Reducing the PWM carrier frequency is effective as a countermeasure against EMI from the inverter or for reducing leakage
current, but doing so increases the motor noise.
• When the PWM carrier frequency is set to 1 kHz or lower (
Pr.72
≤
1), the increase in the harmonic current causes the fast-
response current limit to activate before the stall prevention operation, which may result in torque shortage. In this case,
disable the fast-response current limit in
Pr.156 Stall prevention operation selection
.
Parameters referred to
Pr.156 Stall prevention operation selection
Pr.570 Multiple rating setting
Pr.800 Control method selection
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...