380
15. (A) Application Parameters
15.4 PID control
15.4
PID control
Process control such as flow rate, air volume or pressure are possible on the inverter.
A feedback system can be configured and PID control can be performed with the set point and feed back values set by analog
input signals (terminals 2 and 4) or using parameter values given via communication or by the PLC function.
Pr.
Name
Initial value
Setting range
Description
127
A612
PID control automatic
switchover frequency
9999
0 to 590 Hz
Set the value at which control is automatically switched to PID
control.
9999
No PID control automatic switchover function
128
A610
PID action selection
0
0, 20, 21, 50, 51,
60, 61, 1000,
1001, 1010,
1011, 2000,
2001, 2010, 2011
Select how to input the deviation value, measured value and set
point, and forward and reverse action.
40 to 43
Refer to
129
A613
PID proportional band
100%
0.1% to 1000%
If a narrow proportional band is set (small parameter setting value),
the manipulated amount changes considerably by slight changes in
the measured value. As a result, response improves as the
proportional band becomes narrower, though stability worsens as
shown by the occurrence of hunting. Gain Kp=1/proportional band
9999
No proportional control
130
A614
PID integral time
1 s
0.1 to 3600 s
With deviation step input, this is the time (Ti) used for obtaining the
same manipulated amount as proportional band (P) by only integral
(I) action. Arrival to the set point becomes quicker the shorter an
integral time is set, though hunting is more likely to occur.
9999
No integral control
131
A601
PID upper limit
9999
0% to 100%
Set the upper limit. The FUP signal is output when the feedback
value exceeds this setting. The maximum input (20 mA/5 V/10 V) of
the measured value is equivalent to 100%.
9999
No function
132
A602
PID lower limit
9999
0% to 100%
Set the lower limit. The FDN signal is output when the measured
value falls below the setting range. The maximum input (20 mA/5 V/
10 V) of the measured value is equivalent to 100%.
9999
No function
133
A611
PID action set point
9999
0% to 100%
Set the set point during PID control.
9999
Set point set by
Pr.128
.
134
A615
PID differential time
9999
0.01 to 10 s
With deviation ramp input, this is the time (Td) used for obtaining the
manipulated amount only by proportional action (P). Response to
changes in deviation increase greatly as the differential time
increases.
9999
No differential control
553
A603
PID deviation limit
9999
0% to 100%
The Y48 signal is output when the absolute value of the deviation
exceeds the deviation limit value.
9999
No function
554
A604
PID signal operation
selection
0
0 to 3, 10 to 13
The action when the upper or lower limit for a measured value input
is detected or when a limit for the deviation is detected can be
selected. The operation for PID output suspension function can be
selected.
575
A621
Output interruption
detection time
1 s
0 to 3600 s
When the output frequency after PID calculation stays less than the
Pr.576
setting for the time set in
Pr.575
or more, the inverter
operation is suspended.
9999
No output interruption function
576
A622
Output interruption
detection level
0 Hz
0 to 590 Hz
Set the frequency at which output interruption is performed.
577
A623
Output interruption
cancel level
1000%
900% to 1100%
Level at which the PID output suspension function is released. Set
"
Pr.577
- 1000%".
609
A624
PID set point/deviation
input selection
2
2
The set point or deviation value is input through terminal 2.
3
The set point or deviation value is input through terminal 4.
4
The set point or deviation value is input via communication.
5
The set point or deviation value is input by the PLC function.
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...