420
15. (A) Application Parameters
15.12 Trace function
2.
Tracing
Sampling starts according to the
Pr.1020 and Pr.1024
settings.
The trace status can be monitored. (Refer to
3.
Waveform check
By using FR Configurator2, trace data stored in the internal RAM can be displayed on a computer screen. For
details, refer to the Instruction Manual of FR Configurator2.
Selection of sampling time (Pr.1022, Pr.1023)
• The sampling time is determined by the sampling cycle and the number of data acquisition points. The the number of data
acquisition points varies depending on the setting in
Pr.1023 Number of analog channels
.
Analog source (monitor item) selection
• Select the analog sources (monitor items) to be set to
Pr.1027 to Pr.1034
from the following table.
Pr.1023
Number of analog channels
Memory mode sampling time
Number of data
acquisition points
Minimum (Pr.1022 = "1")
Maximum (Pr.1022 = "1000")
1
1704 ms
1704 s
1704
2
1280 ms
1280 s
1280
3
1024 ms
1024 s
1024
4
852 ms
852 s
852
5
728 ms
728 s
728
6
640 ms
640 s
640
7
568 ms
568 s
568
8
512 ms
512 s
512
Setting
value
Minus (-)
display
Trigger
level
criterion
Setting
value
Monitor item
Minus (-)
display
Trigger
level
criterion
1
Output frequency/speed
54
PID deviation
○
2
Output current
61
Motor thermal load factor
3
Output voltage
62
Inverter thermal load factor
5
Frequency setting value/motor
speed setting
67
PID measured value 2
6
Running speed
83
BACnet valid APDU counter (for
the FR-E800-EPA and FR-E800-
SCEPA only)
65535
7
Motor torque
91
PID manipulated amount
○
8
Converter output voltage
97
Dancer main set speed
9
Regenerative brake duty
201
*Output frequency
Pr.84
10
Electronic thermal O/L relay load
factor
202
*U-phase output current
○
ND rated
current
11
Output current peak value
203
*V-phase output current
○
ND rated
current
12
Converter output voltage peak
value
204
*W-phase output current
○
ND rated
current
13
Input power
205
Converter output voltage
400/800/
1000 V
14
Output power
206
*Output current (all three phases)
ND rated
current
17
Load meter
207
*Excitation current (A)
ND rated
current
18
Motor excitation current
208
*Torque current (A)
ND rated
current
19
Position pulse
65535
209
Terminal 2
100%
20
Cumulative energization time
65535
210
Terminal 4
100%
23
Actual operation time
65535
212
*Excitation current (%)
○
100%
24
Motor load factor
213
*Torque current (%)
○
100%
32
Torque command
230
*Output frequency (signed)
○
Pr.84
33
Torque current command
231
*Motor speed (with sign)
○
35
Feedback pulse
65535
232
*Speed command (with sign)
○
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...