NOTE
• The PM sensorless vector control requires the following conditions.
• For the motor capacity, the rated motor current should be equal to or less than the rated inverter current. (Note that the motor
rated current should be 0.4 kW or higher (0.1 kW or higher for the 200 V class).)
If a motor with substantially low rated current compared with the inverter rated current is used, speed and torque accuracies
may deteriorate due to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated current.
• Offline auto tuning is performed.
• Single-motor operation (one motor to one inverter) is performed.
• The overall wiring length with the motor must be 100 m or less. (For the wiring length, refer to the Instruction Manual
(Connection).)
• A surge voltage suppression filter (FR-ASF/FR-BMF) is not used.
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...