4. Control Method
4.2 Changing the control method and mode
• To enable the control method and the control mode selected in
Pr.800 (Pr.451)
, the condition to start operation must be
satisfied as shown in the following table. Otherwise the operation does not start due to the setting error (SE) alarm when
the start signal is input.
*1
The control method depends on the motor selected in
Pr.71 (Pr.450)
: Real sensorless vector control for the induction motor, and PM sensorless
vector control for the PM motor.
*2
Operation can start regardless of the setting.
*3
A Vector control compatible option is required.
Automatic parameter setting by changing the Pr.800 setting
• The
Pr.10
and
Pr.22
settings are automatically changed when the control method is changed.
• When the control method is changed from V/F control or Advanced magnetic flux vector control to Vector control, the
Pr.10
setting is automatically changed as follows.
• When the control method is changed from Vector control to V/F control or Advanced magnetic flux vector control, the
Pr.10
setting is automatically changed as follows.
• When the control method is changed from V/F control or Advanced magnetic flux vector control to Real sensorless vector
control or Vector control, the
Pr.22
setting is automatically changed as follows (only for the ND rating in the FR-E820-
0175(3.7K) or lower, FR-E840-0095(3.7K) or lower, FR-E860-0061(3.7K) or lower, and FR-E820S-0110(2.2K) or lower).
• When the control method is changed from Real sensorless vector control or Vector control to V/F control or Advanced
magnetic flux vector control, the
Pr.22
setting is automatically changed as follows (only for the ND rating in the FR-E820-
0175(3.7K) or lower, FR-E840-0095(3.7K) or lower, FR-E860-0061(3.7K) or lower, and FR-E820S-0110(2.2K) or lower).
Pr.800
setting
Pr.451
setting
Control method
Control mode
Condition to start operation
MC signal
Pr.80 (Pr.453),
Pr.81 (Pr.454)
setting
Pr.71
(Pr.450)
0
—
Vector control
Speed control
Other than 9999
Induction
motor
—
1
—
Torque control
—
2
—
Speed control / torque
control switchover
ON: Torque
control OFF:
Speed control
9
—
Vector control test operation
—
10
Real sensorless vector control /
PM sensorless vector control
Speed control
—
—
11
Real sensorless vector control
Torque control
Induction
motor
—
12
Speed control / torque
control switchover
ON: Torque
control OFF:
Speed control
19
—
PM sensorless vector control test operation
PM motor
—
20
Advanced magnetic flux vector
control
Speed control
Induction
motor
—
40 (initial
value)
40
V/F control
—
—
—
—
9999
(initial
value)
Control method and control mode selected in
Pr.800
(provided that they are selectable with
Pr.451
)
Pr.
Setting value before change
Setting value after change
10
3 Hz (initial value)
0.5 Hz
Pr.
Setting value before change
Setting value after change
10
0.5 Hz
3 Hz (initial value)
Pr.
Setting value before change
Setting value after change
22
150% (initial setting)
200%
Pr.
Setting value before change
Setting value after change
22
200%
150% (initial setting)
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...