15. (A) Application Parameters
15.7 Automatic restart after instantaneous power failure / flying start with an induction motor
Restart operation without frequency search (Pr.162 = "1 or 11")
• When
Pr.162
= "1 or 11" while the encoder feedback control is disabled, reduced voltage start is used for the restart
operation. In this method, the voltage is raised gradually while keeping the output frequency level at the level before an
instantaneous power failure, regardless of the motor's coasting speed.
NOTE
• This restart method uses the output frequency that was active before the instantaneous power failure stored in memory. If the
instantaneous power failure time is 0.2 second or more, the output frequency can no longer be stored and held in memory, so
the restart is performed from
Pr.13 Starting frequency
(initial value: 0.5 Hz).
• During Real sensorless vector control, the operation is the same as one when
Pr.162
= "0 or 10".
Restart operation with encoder detection frequency search (Pr.162 = "1
or 11")
• When "1 or 11" is set in
Pr.162
by encoder feedback control, the inverter is restarted by the motor speed and direction of
rotation that were detected by the encoder at the power restoration.
• The
Pr.299 Rotation direction detection selection at restarting
setting is invalid by encoder detection frequency
search.
NOTE
• Under Vector control, encoder detection frequency search is used regardless of the
Pr.162
setting. The
Pr.58 and Pr.299
settings are invalid at this time.
• For the encoder feedback control, refer to
.
• During Real sensorless vector control, the operation is the same as one when
Pr.162
= "0 or 10".
Instantaneous (power failure) time
Coasting time
Pr.57
setting
Restart cushion time
(
Pr.58
setting)
Power supply
(R/L1, S/L2,
T/L3)
Motor speed N
(r/min)
Inverter output
frequency f(Hz)
Inverter output
voltage E(V)
* The output shut off timing differs according to the load condition.
*
V/F control, Advanced magnetic flux vector control
Instantaneous (power failure) time
Power supply
(R/L1, S/L2, T/L3)
Motor speed N
(r/min)
Inverter output
frequency f(Hz)
Output voltage E(V)
Coasting
time (
Pr.57
)
Acceleration time
at a restart (
Pr.611
)
The output shut off timing differs according to the load condition.
Restart cushion time (
Pr.58
)
V/F control, Advanced magnetic flux vector control
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...