14. (C) Motor Constant Parameters
14.3 Offline auto tuning for a PM motor (motor constant tuning)
711
C131
Motor Ld decay ratio
9999
0% to 100%, 9999
Tuning data (The value measured by offline auto tuning is
automatically set.)
9999: Inverter internal data is used.
712
C132
Motor Lq decay ratio
9999
0% to 100%, 9999
717
C182
Starting resistance tuning
compensation coefficient 1
9999
0% to 200%, 9999
721
C185
Starting magnetic pole
position detection pulse
width
9999
0 to 6000
μ
s, 9999
725
C133
Motor protection current
level
9999
100% to 500%
Set the maximum current (OCT) level of the motor.
9999
200%
1002
C150
Lq tuning target current
adjustment coefficient
9999
50% to 150%
Adjust the target current during tuning.
9999
100%
450
C200
Second applied motor
9999
0, 3, 5, 6, 10, 13, 15, 16,
20, 23, 30, 33, 40, 43, 50,
53, 70, 73, 1800, 1803,
8090, 8093, 9090, 9093
Set this parameter when using the second motor
(the same specifications as
Pr.71
).
9999
The function is disabled.
453
C201
Second motor capacity
9999
0.1 to 30 kW
Set the capacity of the second motor.
9999
V/F control
454
C202
Number of second motor
poles
9999
2, 4, 6, 8, 10, 12
Set the number of poles of the second motor.
9999
V/F control
51
C203
Second electronic thermal
O/L relay
9999
0 to 500 A
Set the rated current of the second motor.
9999
The second electronic thermal O/L relay is disabled.
456
C204
Rated second motor
voltage
200/400/
575 V
0 to 1000 V
Set the rated voltage (V) of the second motor.
457
C205
Rated second motor
frequency
9999
10 to 400 Hz
Set the rated frequency (Hz) of the second motor.
9999
Inverter internal data is used.
743
C206
Second motor maximum
frequency
9999
0 to 400 Hz
Set the permissible speed (frequency) of the second motor.
9999
The
Pr.457
setting is used.
744
C207
Second motor inertia
(integer)
9999
10 to 999, 9999
Set the motor inertia of the second motor.
9999: Inverter internal data is used.
745
C208
Second motor inertia
(exponent)
9999
0 to 7, 9999
463
C210
Second motor auto tuning
setting/status
0
0
No auto tuning for the second motor.
1
Offline auto tuning is performed without the second motor
rotating.
11
Offline auto tuning is performed without the second motor
rotating (under V/F control).
458
C220
Second motor constant
(R1)
9999
0 to 50
Ω
, 9999
Tuning data of the second motor.
(The value measured by offline auto tuning is automatically
set.)
9999: Inverter internal data is used.
460
C222
Second motor constant
(L1) / d-axis inductance (Ld)
9999
0 to 500 mH, 9999
461
C223
Second motor constant
(L2) / q-axis inductance (Lq)
9999
0 to 500 mH, 9999
860
C226
Second motor torque
current/Rated PM motor
current
9999
0 to 500 A, 9999
738
C230
Second motor induced
voltage constant (phi f)
9999
0 to 5000 mV (rad/s)
Set this parameter according to the PM motor
specifications.
9999
The value calculated from the parameter setting for motor
constant is used.
1413
C235
Second motor induced
voltage constant (phi f)
exponent
9999
0 to 2
Set the exponent n when the induced voltage constant phi
f (
Pr.738
) is multiplied by 10
n
.
9999
No exponent setting
Pr.
Name
Initial
value
Setting range
Description
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...