12. (M) Item and Output Signal for Monitoring
12.6 Output terminal function selection
Assignment of output signals
• The signals can be assigned to the open collector output terminals (2 terminals) and relay output terminal (1 terminal),
which are provided as the output terminals of the inverter. (The open collector output terminals are provided only with the
standard model.)
• The signals can be output via communication, or assigned to the extension terminals of the plug-in option (FR-A8AY or
FR-A8AR).
○
: Assignment/output available,
─
: Assignment/output unavailable (no function)
*1
The communication protocol affects which terminal can be used. For details, refer to the Instruction Manual (Communication) or the Instruction
Manual of the communication option.
*2
Refer to the Instruction Manual of the option for details on the option output terminals.
Output signal list
• A function listed below can be set to each output terminal.
• Refer to the following table and set the parameters. (0 to 99, 200 to 299: Positive logic, 100 to 199, 300 to 399: Negative
logic)
Pr.
Terminal
name
External output terminal
(physical terminal)
Output via
communication
Option output terminal (physical
terminal)
FR-E800
FR-E800-
(SC)E
FR-A8AY
FR-A8AR
190
RUN
○
—
○
—
—
191
FU
○
—
○
—
—
192
A,B,C
○
○
○
—
—
193
NET Y1
—
—
○
—
—
194
NET Y2
—
—
○
—
—
195
NET Y3
—
—
○
—
—
196
NET Y4
—
—
○
—
—
313
DO0
—
—
○
○
—
314
DO1
—
—
○
○
—
315
DO2
—
—
○
○
—
316
DO3
—
—
—
○
—
317
DO4
—
—
—
○
—
318
DO5
—
—
—
○
—
319
DO6
—
—
—
○
—
320
RA1
—
—
—
—
○
321
RA2
—
—
—
—
○
322
RA3
—
—
—
—
○
Setting
Signal
name
Function
Operation
Related
parameter
Refer to page
Positive
logic
Negative
logic
0
100
RUN
Inverter running
Output during operation when the inverter
output frequency reaches
Pr.13 Starting
frequency
or higher.
—
1
101
SU
Up to frequency
Output when the output frequency reaches
the set frequency.
Pr.41
3
103
OL
Overload warning
Output while the stall prevention function
works.
Pr.22, Pr.23,
Pr.66, Pr.154
4
104
FU
Output frequency
detection
Output when the output frequency reaches
the frequency set in
Pr.42
(
Pr.43
during
reverse rotation) or higher.
Pr.42, Pr.43
7
107
RBP
Regenerative brake
prealarm
Output when the regenerative brake duty
reaches 85% of the setting of
Pr.70
.
Pr.70
8
108
THP
Electronic thermal O/L
relay pre-alarm
Output when the cumulative electronic
thermal O/L relay value reaches 85% of the
trip level. (The electronic thermal O/L relay
function (E.THT/E.THM) is activated when
the value reaches 100%.)
Pr.9
11
111
RY
Inverter operation ready
Output when the reset process is completed
after powering ON the inverter or when the
inverter is ready to start operation with the
start signal ON or during operation.
—
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...