10. (D) Operation Command and Frequency Command
10.1 Operation mode selection
Switching the operation mode by external signals (X65, X66 signals)
• When
Pr.79
= "0, 2 or 6", the PU operation mode and External operation modes can be changed to the Network operation
mode during a stop (during motor stop, start command OFF) by the PU/NET operation switchover (X65) signal, or the
External/NET operation switchover (X66) signal. (When
Pr.79
= "6", switchover is enabled during operation.)
• To switch between the Network operation mode and the PU operation mode
1.
Set
Pr.79
= "0 (initial value) or 6".
2.
Set
Pr.340 Communication startup mode selection
= "10".
3.
Set "65" in any parameter from
Pr.178 to Pr.184
to assign the PU/NET operation switchover (X65) signal to a
terminal.
4.
When the X65 signal is ON, the PU operation mode is selected. When the X65 signal is OFF, the NET operation
mode is selected.
*1
When the X66 signal is ON, the NET operation mode is selected.
*2
When the X16 signal is OFF, the PU operation mode is selected. Also, when "0" is set for
Pr.550 NET mode operation command source
selection
and the communication option is not connected (communication option is the command source), the PU operation mode is selected.
When the X16 signal is ON, the External operation mode is selected.
• To switch between the Network operation mode and the External operation mode
1.
Set
Pr.79
= "0 (initial value), 2, 6, or 7". (When
Pr.79
= "7" and the X12 (MRS) signal is ON, the operation mode can
be switched.)
2.
Set
Pr.340 Communication startup mode selection
= "0" (initial value) or "1".
3.
Set "66" in one of
Pr.178 to Pr.184
to assign the NET-External operation switching signal (X66) to a terminal.
4.
When the X66 signal is ON, the NET operation mode is selected. When the X66 signal is OFF, the External
operation mode is selected.
*1
When
Pr.550 NET mode operation command source selection
= "0" (communication option control source) and no communication option is
connected, the External operation mode is selected.
*2
When the X16 signal is OFF, the PU operation mode is selected. Also, when the X65 signal is assigned, the operation mode follows the ON/OFF
state of the X65 signal.
Pr.340
setting
Pr.79 setting
X65 signal state
Remarks
ON (PU)
OFF (NET)
10
0 (initial value)
PU operation mode
NET operation mode
—
1
PU operation mode
Fixed at PU operation mode.
2
NET operation mode
Fixed at NET operation mode.
3, 4
External/PU combined operation mode
Fixed at External/PU combined operation mode.
6
PU operation mode
NET operation mode
The operation mode can be changed during
operation.
7
X12 (MRS)
ON
Switching between the External operation mode
and PU operation mode is enabled.
The signal is OFF during operation in the External
operation mode.
X12 (MRS)
OFF
External operation mode
The operation mode is forcibly switched to the
External operation mode.
Pr.340
setting
Pr.79 setting
X66 signal state
Remarks
ON (NET)
OFF (External)
0 (initial
value), 1
0 (initial value)
NET operation mode
External operation
mode
—
1
PU operation mode
Fixed at PU operation mode.
2
NET operation mode
External operation
mode
Switching to PU operation mode is disabled.
3, 4
External/PU combined operation mode
Fixed at External/PU combined operation mode.
6
NET operation mode
External operation
mode
The operation mode can be changed during
operation.
7
X12 (MRS)
ON
NET operation mode
External operation
mode
The signal is OFF during operation in the External
operation mode.
X12 (MRS)
OFF
External operation mode
The operation mode is forcibly switched to the
External operation mode.
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...