41
2. Basic Operation
2.6 Basic operation procedure (External operation)
1
2
3
4
5
6
7
8
9
10
NOTE
• When both the forward rotation start switch (STF signal) and the reverse rotation start switch (STR signal) are turned ON, the
motor cannot be started. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
• The initial value is 60 Hz for terminal RH in Group 1 (50 Hz in Group 2), 30 Hz for terminal RM, and 10 Hz for terminal RL. (To
change the settings, use
Pr.4, Pr.5
, and
Pr.6
, respectively.)
• In the initial setting, if two or more speed switches (signals) are simultaneously turned ON, priority is given to the switch (signal)
for the lower speed. For example, when both RH and RM signals turn ON, the RM signal (
Pr.5
) has the higher priority.
• Up to 15-speed switching operation can be performed.
• Up to two external input terminals are available for the Ethernet model. Use
Pr.178 STF/DI0 terminal function selection
and
Pr.179 STR/DI1 terminal function selection
to assign the functions to terminals DI0 and DI1.
Parameters referred to
Pr.4 to Pr.6 (multi-speed setting)
Pr.7 Acceleration time, Pr.8 Deceleration time
Pr.178 STF/DI0 terminal function selection, Pr.179 STR/DI1 terminal function selection
2.6.3
Setting the frequency using an analog signal
(voltage input)
• Turn ON the STF/STR signal to give a start command.
• Use the frequency setting potentiometer to give a frequency command (by connecting it across terminals 2 and 5 (voltage
input)).
[Connection diagram]
(The inverter supplies 5 V power to the frequency setting potentiometer via terminal 10.)
The following shows the procedure to operate at 60 Hz.
Operating procedure
1.
Turning ON the power of the inverter
The operation panel is in the monitor mode.
2.
Start
Turn ON the start switch (STF/STR signal). The RUN LED on the operation panel blinks as no frequency command
is given.
3.
Acceleration
→
constant speed
Turn the frequency setting potentiometer clockwise slowly to full. The frequency value on the monitor increases
according to the setting of
Pr.7 Acceleration time
, and "60.00" (60.00 Hz) appears on the monitor. The RUN LED
is ON during forward rotation and blinks slowly during reverse rotation.
4.
Deceleration
Turn the frequency setting potentiometer counterclockwise slowly to full. The frequency value on the monitor
decreases according to the setting of
Pr.8 Deceleration time
, "0.00" (0.00 Hz) appears on the monitor, and the
motor stops rotating. The RUN LED blinks.
5.
Stop
Turn OFF the start switch (STF/STR signal). The RUN LED turns OFF.
Inverter
Frequency setting
potentiometer
5
10
2
Forward rotation start
Reverse rotation start
STF
STR
SD
Switch
Potentiometer
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...