15. (A) Application Parameters
15.4 PID control
Connection diagram
*1
Prepare a power supply matched to the power supply specifications of the detector.
*2
The applied output terminals differ by the settings of
Pr.190 to Pr.196 (Output terminal function selection)
.
*3
The applied input terminals differ by the settings of
Pr.178 to Pr.189 (Input terminal function selection)
Assigning the PID control valid (X14)
signal to an input terminal enables PID control to be performed only when the X14 signal is turned ON.
*4
The AU signal need not be input.
Selection of deviation value, measured value and set point input method,
and PID action method (Pr.128, Pr.609, Pr.610)
• Using
Pr.128
, select the input method for the PID set point, measured value detected by the meter, and externally
calculated deviation. Also, select forward or reverse action.
• Sink logic
•
Pr.128
= "20"
•
Pr.182
= "14"
•
Pr.190
= "15"
•
Pr.191
= "14"
•
Pr.192
= "16"
Power supply
MCCB
Inverter
Forward
rotation
Reverse
rotation
PID control
selection
Setting
Potentiometer
(Set point setting)
0 24V
Power
supply
*1
AC1φ
200/220V 50/60Hz
R/L1
S/L2
T/L3
STF
STR
RH(X14)
*3
SD
10
2
5
4
U
V
W
*2
(FUP)RUN
*2
(FDN)FU
SE
(Measured value) 4 to 20mA
Motor
M
Pump
P
Upper limit
Lower limit
Output signal common
2-wire type
Detector
3-wire
type
-
+
+
+
-
(OUT)
(24V
Forward rotation
output
Reverse rotation
output
*2
(RL)ABC
(COM)
*4
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...