10. (D) Operation Command and Frequency Command
10.3 Start command source and frequency command source during communication operation
• The following table shows the command interface for each function in the Network operation mode, determined by the
parameter settings: an external terminal or a communication interface (PU connector, Ethernet connector, or
communication option).
Pr.338 Communication operation command source
0: NET
1: EXT
Remarks
Pr.339 Communication speed command source
0:
NET
1:
EXT
2:
EXT
0:
NET
1:
EXT
2:
EXT
Frequency setting through communication
NET —
NET NET —
NET
Terminal 2
—
EXT —
—
EXT —
Terminal 4
—
EXT
—
EXT
RL
Low-speed operation command/Remote setting
(setting clear)/Stop-on-contact selection 0
NET EXT
NET EXT
Pr.59
= "0" (multi-speed),
Pr.59
≠
"0" (remote),
Pr.270
="1" (stop-
on-contact)
Middle-speed operation command/Remote
setting (deceleration)
NET EXT
NET EXT
RH
High-speed operation command/ Remote setting
(acceleration)
NET EXT
NET EXT
Second function selection/ Stop-on-contact
selection 1
NET
EXT
Pr.270
= "1" (stop-on-contact)
Terminal 4 input selection
—
Combined
—
Combined
JOG
Jog operation selection
—
EXT
External thermal relay input
EXT
15-speed selection
NET EXT
NET EXT
Pr.59
="0" (multi-speed)
X10
Inverter run enable
EXT
X12
PU operation external interlock
EXT
X13
External DC injection brake operation start
NET
EXT
X14
PID control valid
NET EXT
NET EXT
Brake opening completion
NET
EXT
X16
PU/External operation switchover
EXT
X18
V/F switchover
NET
EXT
Pre-excitation
NET
EXT
Output stop
Combined
EXT
Pr.79
≠
"7"
PU operation interlock
EXT
Pr.79
= "7".
When X12 signal is not assigned.
STP
(STOP)
Start self-holding selection
—
EXT
Control mode switchover
NET
EXT
TL
Torque limit selection
NET
EXT
JOG2
NET
EXT
X37
Traverse function selection
NET
EXT
X42
Torque bias selection 1
NET
EXT
X43
Torque bias selection 2
NET
EXT
TRG
Trace trigger input
Combined
EXT
Trace sampling start/end
Combined
EXT
SQ
Sequence start
EXT or NET
EXT
Pr.414
= "1": Valid when there is
external or network input.
Pr.414
= "2": External.
X51
Fault clear
Combined
EXT
Forward rotation command
NET
EXT
Reverse rotation command
NET
EXT
Inverter reset
EXT
X65
PU/NET operation switchover
EXT
X66
External/NET operation switchover
EXT
X67
Command source switchover
EXT
X72
PID P control switchover
NET EXT
NET EXT
X74
Magnetic flux decay output shutoff
NET
EXT
X92
Emergency stop
Combined
EXT
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...