230
10. (D) Operation Command and Frequency Command
10.3 Start command source and frequency command source during communication operation
*1
Use
Pr.178 to Pr.189 (Input terminal function selection)
to assign the function to an input terminal. (Refer to
NOTE
• The communication interface selection is determined by the setting of
Pr.550
and
Pr.551
.
• The settings of
Pr.338
and
Pr.339
can be changed during operation when
Pr.77
= "2". Note that the changed setting is applied
after the inverter has stopped. Until the inverter has stopped, the previous setting of the interface for the operation command
and the speed command in the Network operation mode is valid.
Changing the command interface using a signal input via external
terminal (X67 signal)
• In the Network operation mode, the command interface for the operation command and the speed command can be
changed using the Command source switchover (X67) signal. This method may be useful to use both external terminal
and communication interface by using a different interface according to the command type.
• For the X67 signal, set "67" to any parameter from
Pr.178 to Pr.184 (Input terminal function selection)
to assign the
function to a control terminal.
• When the X67 signal is OFF, the command interface for the operation command and the speed command is the control
terminal.
NOTE
• The ON/OFF state of the X67 signal is applied only during a stop. When the terminals are switched during operation, the ON/
OFF state is reflected after a stop.
• When the X67 is OFF, a reset via communication is disabled.
• Changing the terminal assignment using
Pr.178 to Pr.184 (Input terminal function selection)
may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.59 Remote function selection
Pr.79 Operation mode selection
[Explanation of Terms in Table]
EXT: External terminal only
NET: Communication interface only
Combined: Either external terminal or communication interface
—: Neither external terminal nor communication interface
X67 signal state
Interface for the operation command
Interface for the speed command
Signal not assigned
Determined by
Pr.338
setting
Determined by
Pr.339
setting
ON
OFF
Control terminal only
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...