310
13. (T) Multi-Function Input Terminal Parameters
13.1 Analog input selection
13
(T) Multi-Function Input Terminal Parameters
13.1
Analog input selection
The functions to switch the analog input terminal specifications and forward/reverse rotation by the input signal polarity are
selectable.
Purpose
Parameter to set
Refer to
page
To inverse the rotation direction with the
voltage/current analog input selection
(terminals 2 and 4)
Analog input selection
P.T000, P.T001
Pr.73, Pr.267
To assign functions to analog input
terminals
Terminal 4 function assignment P.T040
Pr.858
To eliminate noise on analog inputs
Analog input filter
P.T002 to P.T007
Pr.74, Pr.822, Pr.826,
Pr.832, Pr.836,
Pr.849
To adjust analog input frequency/voltage
(current) (calibration)
Frequency setting voltage
(current) bias and gain
P.T200 to P.T203,
P.T400 to P.T403,
P.M043
Pr.125, Pr.126,
Pr.241, C2 to C7
(Pr.902 to Pr.905)
To adjust analog input torque/voltage
(current) (calibration)
Torque setting voltage (current)
bias and gain
P.T410 to P.T413,
P.M043
Pr.241, C38 to C41
(Pr.932, Pr.933)
To assign functions to input terminals
Input terminal function
selection
P.T700 to P.T711,
P.T740
Pr.178 to Pr.189,
Pr.699
To change the input specification (NO/NC
contact) of input signals
Output stop signal (MRS) /
Inverter run enable signal (X10)
input selection
P.T720
Pr.17
To assign start and forward/reverse
commands to different signals
Start signal (STF/STR) operation
selection
P.G106
Pr.250
Pr.
Name
Initial value
Setting
range
Description
73
T000
Analog input selection
1
0, 1, 10, 11
Switch 2: V (initial
status)
The terminal 2 input specification (0 to 5 V, 0 to 10
V, 0 to 20 mA) is selectable. Also the reversible
operation setting is selectable.
6, 16
Switch 2: I
267
T001
Terminal 4 input
selection
0
0
Switch 4: I (initial
status)
Terminal 4 input, 4 to 20 mA
1
Switch 4 - V
Terminal 4 input, 0 to 5 V
2
Terminal 4 input, 0 to 10 V
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...