12. (M) Item and Output Signal for Monitoring
12.2 Monitor item selection on operation panel or via communication
12.2
Monitor item selection on operation panel or via
communication
The monitor item to be displayed on the operation panel can be selected.
*1
The setting range differs depending on the model. For more information, refer to Monitor item list.
Pr.
Name
Initial value
Setting range
Description
52
M100
Operation panel main
monitor selection
0 (output
frequency)
0, 5 to 14, 17 to
20, 23 to 25, 32,
33, 35, 38, 40 to
42, 44, 45, 50 to
57, 61, 62, 67,
83, 91, 97,
100
Select the monitor item to be displayed on the operation
panel.
Refer to
for the monitor item selection.
774
M101
Operation panel monitor
selection 1
9999
1 to 3, 5 to 14,
17 to 20, 23 to
25, 32, 33, 35,
38, 40 to 42, 44,
45, 50 to 57, 61,
62, 67, 83, 91,
97, 100, 9999
Each of the initial monitor items displayed on the operation
panel in the monitor mode (output frequency, output current,
and output voltage) can be switched to a user-designated
item.
9999: Follows the
Pr.52
setting.
775
M102
Operation panel monitor
selection 2
776
M103
Operation panel monitor
selection 3
992
M104
Operation panel setting dial
push monitor selection
0 (set frequency)
0 to 3, 5 to 14,
17 to 20, 23 to
25, 32, 33, 35,
38, 40 to 42, 44,
45, 50 to 57, 61,
62, 67, 91, 97,
100
Select the monitor item displayed on the operation panel at
the time when the setting dial is pressed. (Available for the
standard model only.)
170
M020
Watt-hour meter clear
9999
0
Set "0" to clear the watt-hour meter.
10
Set "10" to monitor the cumulative power in the range of 0 to
9999 kWh via communication.
9999
Set "9999" to monitor the cumulative power in the range of
0 to 65535 kWh via communication.
563
M021
Energization time carrying-
over times
0
(0 to 65535)
(Read-only)
The number of times that the cumulative energization time
exceeded 65535 hours is displayed (read-only).
268
M022
Monitor decimal digits
selection
9999
0
Value is displayed in 1 increments (an integer).
1
Value is displayed in 0.1 increments.
9999
No function
891
M023
Cumulative power monitor
digit shifted times
9999
0 to 4
Set the number of digits to move the decimal point of the
cumulative energy monitored value to the left. The readout
peaks out at the upper limit of readout.
9999
The function of moving the decimal point is not available.
The readout is reset to 0 when it exceeds the upper limit.
171
M030
Operation hour meter clear
9999
0
Set "0" to clear the operation hour meter.
9999
The readout is always 9999. Nothing changes when "9999"
is set.
564
M031
Operating time carrying-
over times
0
(0 to 65535)
(Read-only)
The number of times that the operating time reaches 65535
hours is displayed. Read-only.
290
M044
Monitor negative output
selection
0
0, 1, 4, 5, 8, 9,
12, 13
Set the availability of negative signal output via terminal AM,
through communication, and to the FR-A8AY. (Refer to
.)
1106
M050
Torque monitor filter
9999
0 to 5 s
The filter time constant is selectable for monitoring of the
torque. A larger setting results in slower response.
9999
0.3 s filter
1107
M051
Running speed monitor
filter
9999
0 to 5 s
The filter time constant is selectable for monitoring of the
running speed. A larger setting results in slower response.
9999
0.08 s filter
1108
M052
Excitation current monitor
filter
9999
0 to 5 s
The filter time constant is selectable for monitoring of the
motor excitation current. A larger setting results in slower
response.
9999
0.3 s filter
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...