278
12. (M) Item and Output Signal for Monitoring
12.2 Monitor item selection on operation panel or via communication
NOTE
• The number of readout digits of the cumulative energization time (
Pr.52
= "20"), actual operation time (
Pr.52
= "23"),
cumulative energy (
Pr.52
= "25"), and cumulative energy saving (
Pr.52
= "51") does not change.
Enabling display of negative numbers during monitoring (Pr.290)
• Negative values can be used for indication via terminal AM (analog voltage output), on communication options, and via
terminal AM0 (of the FR-A8AY). To check which items can be monitored with indication of negative numbers, refer to
Monitor description list (on
—: Negative numbers indication disabled (positive only)
*1
Negative numbers indication is disabled via RS-485 communication (Mitsubishi inverter protocol or MODBUS RTU).
NOTE
• When indication with negative numbers is enabled for the output via terminal AM/AM0 (analog voltage output), the output is
within the range of -10 to +10 VDC. Connect the meter with which output level is matched.
• The operation panel displays only unsigned numbers.
Monitor filter (Pr.1106 to Pr.1108)
• The response level (filter time constant) of the following monitor indicators can be adjusted. Increase the setting when a
monitor indicator is unstable, for example.
Parameters referred to
Pr.53 Frequency / rotation speed unit switchover
Pr.55 Frequency monitoring reference, Pr.56 Current monitoring reference, Pr.866 Torque monitoring reference
Pr.290 setting
Negative numbers
indication (via terminal AM)
Negative numbers
indication (via
communication option)
Negative numbers indication (via
terminal AM0) (with the FR-A8AY)
0 (initial value)
—
—
—
1
Enabled
—
—
4
—
Enabled
—
5
Enabled
Enabled
—
8
—
—
Enabled
9
Enabled
—
Enabled
12
—
Enabled
Enabled
13
Enabled
Enabled
Enabled
Pr.
Monitor number
Monitor indicator name
1106
7
Motor torque
17
Load meter
32
Torque command
33
Torque current command
1107
6
Motor speed
1108
18
Motor excitation current
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...