12. (M) Item and Output Signal for Monitoring
12.1 Speed indication and its setting change to rotations per minute
12
(M) Item and Output Signal for Monitoring
12.1
Speed indication and its setting change to
rotations per minute
The frequency monitored or set on the operation panel can be changed to the motor speed or the machine speed.
*1
Gr.1 and Gr.2 are the parameter initial value groups. (Refer to
*2
The setting ranges of
Pr.1 (Pr.18), Pr.37, and Pr.505
are limited so that the following formula is satisfied.
Pr.1 (Pr.18) × Pr.37 / Pr.505
< 8388.607
The setting range of Pr.1 (Pr.18) is not limited when the machine speed display is not selected. To display the machine speed, set values which
satisfy the formula.
Displayed unit switchover (Pr.37, Pr.53, and Pr.505)
• The rotation speed or machine speed can be displayed for monitoring or used for parameter setting instead of the
frequency by using
Pr.53
.
Purpose
Parameter to set
Refer to page
To display the motor speed (the
number of rotations per minute).
To switch the unit of measure to set
the operation speed from frequency
to motor speed.
Speed indication and its
setting change to rotations
per minute
P.M000, P.M001,
P.M003
Pr.37, Pr.53, Pr.505
To change the item monitored on the
operation panel
Operation panel monitor item
selection
clearing the cumulative value
during monitoring
P.M020 to P.M023,
P.M030, P.M031,
P.M044, P.M050 to
P.M052, P.M100 to
P.M104
Pr.52, Pr.170,
Pr.171, Pr.268,
Pr.290, Pr.563,
Pr.564, Pr.774 to
Pr.776, Pr.891,
Pr.992, Pr.1106 to
Pr.1108
To change the monitor item whose
data is output via terminal FM or AM
Terminal FM/AM function
selection
P.M040 to P.M042,
P.M044, P.M300,
P.M301
Pr.54, Pr.55, Pr.56,
Pr.158, Pr.290,
Pr.866
To adjust the output via terminal FM
or AM
Terminal FM/AM calibration
P.M310, P.M320,
P.M321, P.M390
Pr.867, C0 (Pr.900),
C1 (Pr.901), Pr.1200
To check the effects of energy saving Energy saving monitoring
P.M023, P.M100,
P.M200 to P.M207,
P.M300, P.M301
Pr.52, Pr.54, Pr.158,
Pr.891 to Pr.899
To assign functions to the output
terminals
Output terminal function
assignment
P.M400, P.M404,
P.M405, P.M410 to
P.M416, P.M420 to
P.M422, P.M431,
P.M451 to P.M454
Pr.190 to Pr.196,
Pr.289
,
Pr.313 to
Pr.322
To detect the output frequency
Up-to-frequency sensitivity
Output frequency detection
Low speed detection
P.M440 to P.M443,
P.M446
Pr.41 to Pr.43,
Pr.865 to Pr.870
To detect the output current
Output current detection
Zero current detection
P.M433, P.M460 to
P.M464
Pr.150 to Pr.153,
Pr.166, Pr.167
To detect the output torque
Output torque detection
P.M470
Pr.864
To use the remote output function
Remote output
P.M500 to P.M502
Pr.495 to Pr.497
Pr.
Name
Initial value
Setting range
Description
Gr.1
Gr.2
37
M000
Speed display
1800
0.01 to 9998
Set a number for the speed of machine operated at
the speed (frequency) set in
Pr.505
.
53
M003
Frequency / rotation
speed unit
switchover
0
0
Frequency displayed
1
Rotation speed displayed
4
Machine speed displayed
505
M001
Speed setting
reference
60 Hz
50 Hz
1 to 590 Hz
Set the reference speed (frequency) for
Pr.37
.
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...