3. Parameters
3.1 Parameter initial value groups
3
Parameters
This chapter explains the function setting for use of this product.
Always read the instructions before use.
The following marks are used to indicate the controls. (Parameters without any mark are valid for all the controls.)
3.1
Parameter initial value groups
• Initial values of parameters of the FR-E800 differ depending on the parameter initial value group. In this Instruction Manual,
Gr.1 indicates the parameter initial value group 1, and Gr.2 indicates the parameter initial value group 2.
• FR-E800 inverters are divided into two groups as shown in the following table.
• The initial values of the following parameters differ depending on the parameter initial value group.
*1
The parameter is available when the plug-in option (FR-A8AX) is installed. For details, refer to the FR-A8AX E kit Instruction Manual.
Mark
Control method
Applied motor
V/F control
Three-phase induction motor
Advanced magnetic flux vector control
Real sensorless vector control
Vector control
PM sensorless vector control
PM motor
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
Sensorless
Sensorless
Sensorless
Vector
Vector
Vector
PM
PM
PM
Parameter initial value groups
Model
Specification
Group 1 (Gr.1)
FR-E800-1
RS-485 communication, terminal FM
FR-E800-5
RS-485 communication, terminal AM
FR-E800-(SC)EPA
Ethernet communication (Protocol group A)
Group 2 (Gr.2)
FR-E800-4
RS-485 communication, terminal AM
FR-E800-(SC)EPB
Ethernet communication (Protocol group B)
Pr.
Name
Initial value
Refer to
page
Gr.1
Gr.2
3
Base frequency
60 Hz
50 Hz
4
Multi-speed setting (high speed)
60 Hz
50 Hz
19
Base frequency voltage
9999
8888
20
Acceleration/deceleration reference frequency
60 Hz
50 Hz
55
Frequency monitoring reference
60 Hz
50 Hz
66
Stall prevention operation reduction starting frequency
60 Hz
50 Hz
125
Terminal 2 frequency setting gain frequency
60 Hz
50 Hz
126
Terminal 4 frequency setting gain frequency
60 Hz
50 Hz
249
Earth (ground) fault detection at start
0
1
301
BCD input gain
60 Hz
50 Hz
303
BIN input gain
60 Hz
50 Hz
505
Speed setting reference
60 Hz
50 Hz
808
Speed limit
60 Hz
50 Hz
1486
Load characteristics maximum frequency
60 Hz
50 Hz
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...