16. (G) Control Parameters
16.2 Base frequency voltage
16.2
Base frequency voltage
Use this function to adjust the inverter outputs (voltage, frequency) to match with the motor rating.
*1
Gr.1 and Gr.2 are the parameter initial value groups. (Refer to
Base frequency setting (Pr.3)
• When operating a standard motor, generally set the rated frequency of the motor in
Pr.3 Base frequency
. When the motor
operation require switching to the commercial power supply, set the power supply frequency in
Pr.3
.
• When the frequency described on the motor rating plate is "50 Hz" only, make sure to set to 50 Hz. When it is set to 60 Hz,
the voltage will drop too much, causing insufficient torque. As a result, the inverter output may be shut off due to overload.
A caution is required especially in case of
Pr.14 Load pattern selection
= "1" (variable torque load).
• When using the Mitsubishi Electric constant torque motor, set
Pr.3
to 60 Hz.
Setting multiple base frequencies (Pr.47)
• To change the base frequency when using a single inverter switching between multiple motors, use
Pr.47 Second V/F
(base frequency)
.
•
Pr.47
is enabled when the RT signal is ON. To input the RT signal, set "3" in any parameter from
Pr.178 to Pr.189 (Input
terminal function selection)
to assign the function.
NOTE
• The RT signal is the Second function selection signal which also enables other second functions. (Refer to
.)
Setting of base frequency voltage (Pr.19)
• Use
Pr.19 Base frequency voltage
to set the base voltage (for example, rated motor voltage).
• When it is set lower than the power supply voltage, maximum output voltage of the inverter will be the voltage set in
Pr.19
.
•
Pr.19
can be used in the following cases.
• To operate a Vector control dedicated motor (SF-V5RU) with V/F control, the setting is as shown in the following table.
Pr.
Name
Initial value
Setting range
Description
Gr.1
Gr.2
3
G001
Base frequency
60 Hz
50 Hz
0 to 590 Hz
Set the frequency at the rated motor torque. (50/60 Hz)
19
G002
Base frequency voltage
9999
8888
0 to 1000 V
Set the base voltage.
8888
95% of the power supply voltage
9999
Same as the power supply voltage
47
G011
Second V/F (base frequency)
9999
0 to 590 Hz
Set the base frequency when the RT signal is ON.
9999
Second V/F disabled
V/F
V/F
V/F
Pr.19
Output frequency
(Hz)
Pr.3
Pr.47
Output voltage (V)
(a) When regenerative driving (continuous regeneration, etc.) is performed frequently
Output voltage will get higher than the specification during the regenerative driving, which may cause overcurrent trip
(E.OC[]) by the increase in motor current.
(b) When the fluctuation of power supply voltage is high
When the power supply voltage exceeds the rated voltage of the motor, fluctuation of rotation speed or overheating
of motor may occur due to excessive torque or increase in motor current.
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...