4. Control Method
4.2 Changing the control method and mode
1
2
3
4
5
6
7
8
9
10
4.2
Changing the control method and mode
Set the control method and the control mode.
V/F control, Advanced magnetic flux vector control, Real sensorless vector control, Vector control, and PM sensorless vector
control are available.
The available control modes are speed control and torque control modes.
• Select a control method and a control mode by setting
Pr.800 (Pr.451) Control method selection
.
• The control mode can be switched using a mode switching signal (MC).
*1
The setting range for the 575 V class is "0, 3, 5, 6, 10, 13, 15, 16, 30, 33, 8090, 8093, 9090, and 9093".
*2
The initial value differs according to the inverter's voltage class (200/400/575 V).
*3
The inverter internal data is used under PM sensorless vector control.
Setting the motor capacity and the number of motor poles (Pr.80, Pr.81)
• Motor specifications (the motor capacity and the number of motor poles) must be set to select Advanced magnetic flux
vector control, Real sensorless vector control, Vector control, or PM sensorless vector control.
• Set the motor capacity (kW) in
Pr.80 Motor capacity
and set the number of motor poles in
Pr.81 Number of motor poles
.
Selection of the control method and the control mode
• Select a control method (and a control mode) from V/F control, Advanced magnetic flux vector control (speed control), Real
sensorless vector control (speed control, torque control), Vector control (speed control, torque control) and PM sensorless
vector control (speed control).
Pr.
Name
Initial value
Setting range
Description
71
C100
Applied motor
0
0, 3, 5, 6, 10, 13, 15,
16, 20, 23, 30, 33, 40,
43, 50, 53, 70, 73,
1800, 1803, 8090,
8093, 9090, 9093
By selecting a standard motor or constant-torque motor,
the thermal characteristic and motor constant of each
motor are set.
80
C101
Motor capacity
9999
0.1 to 30 kW
Set the applied motor capacity.
9999
No motor capacity setting
81
C102
Number of motor poles
9999
2, 4, 6, 8, 10, 12
Set the number of motor poles.
9999
No number of motor poles setting
83
C104
Rated motor voltage
200/400/575
V
0 to 1000 V
Set the rated motor voltage (V).
84
C105
Rated motor frequency
9999
10 to 400 Hz
Set the rated motor frequency (Hz).
9999
The setting value of
Pr.3 Base frequency
is used.
800
G200
Control method selection
40
0 to 2
Vector control
9
Vector control test operation
10
Real sensorless vector control / PM sensorless vector
control
11, 12
Real sensorless vector control
19
PM sensorless vector control test operation
20
Advanced magnetic flux vector control
40
V/F control
451
G300
Second motor control
method selection
9999
10
Real sensorless vector control / PM sensorless vector
control
11, 12
Real sensorless vector control
20
Advanced magnetic flux vector control
40
V/F control
9999
Control selected in
Pr.800
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...