EN UG-020 Link 6 user guide r1.0
40
Emergency stop inputs
Emergency stop devices must comply with ISO 13850:2015.
Link 6 requires an emergency stop device with two (2)
Normally Closed (NC)
redundant contacts.
The terminal connections belong to the SAFETY - ESTOP terminal group.
Table 29: Emergency stop terminal connections
Label
Purpose
AI
24 V wetting port
A2
Channel A - digital input
B1
24 V output
B2
Channel B - digital input
A typical installation involves a teach pendant that is connected on the front panel. The
emergency stop is an integrated part of the teach pendant. The only thing to do is to install a
jumper wire on A1, A2, B1, and B2.
Figure 36: Terminal connections with jumper on A1, A2, B1, and B2 when the teach pendant is
connected