HLP-C100 Series
HLP-C100 Series Operating Manual
-
63
-
Function: Damping gain factor can help to improve the response speed of the
DC link of the f requency converter making the DC loop signal more
smooth.
C14.08 Function Description
Range
Unit
Default Setting
Damping Gain Factor
0~200
%
96
Option: [0] Trip, f requency converter trips;
[1] Warning, f requency converter issues a warning (but continues to
run);
[2] Disabled, no action is taken;
Function: Select actions when a severe mains imbalance is detected.
C14.12
Function Description
Range Unit Default Setting
Function at Mains Imbanlance
0~2
0
C14.1* Mains On/Off
Option: [0] Manual reset, perform reset via [reset]-button or digital inputs;
[1] - [10] Auto reset 1-10, can perform 1-10 automatic resets af ter trips;
[11] Auto reset11, can perform 15 automatic resets af ter trips;
[12] Auto reset12, can perform 20 automatic resets af ter trips;
[13] In
fi
nite auto reset, can perform an in
fi
nite number of automatic
resets af ter tripping;
Function: Select reset f unction af ter tripping. Once auto reset is selected, the
f requency converter will be restarted af ter an alarm. If reset have
been done and the running signal is active, f requency converter will
restart automatically.
Attention: If the auto reset mode is selected, the f requency converter may
possibly restart automatically af ter the alarm disappear.
C14.20
Function Description
Range
Unit
Default Setting
Reset Mode
0~13
0
C14.2* Trip Reset
normal speed (50/60HZ). Another advantage with overmodulation
is the ability of staying at a constant speed even though mains fault
occurs.