HLP-C100 Series Operating Manual
HLP-C100 Series
-
48
-
C03.84 Function Description
Range
Unit
Default Setting
Ramp5 Type
0~2
0
Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
C03.70
Function Description
Range
Unit
Default Setting
Ramp4 Type
0~2
0
Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
C03.71
Function Description
Range
Unit Default Setting
Ramp4 Ramp up Time
0.10~300.00
S
*
Function: Enter acceleration time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.72
Function Description
Range
Unit Default Setting
Ramp4 Ramp Down Time 0.10~300.00
S
*
Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
C03.7* Ramp4
C03.80
Function Description
Range
Unit
Default Setting
Jog Ramp Time
0.10~300.00
S
*
Function: Enter the time required motor speed f rom 0Hz up to rated motor
speed (C01.25) or f rom the rated motor speed (C01.25) down to 0Hz.
Description of Choice: Jog ramp time starts upon activation of a jog signal via
a selected digital input or serial communication port. See C05.1, choose
[14].
C03.8* Other Ramps