HLP-C100 Series
HLP-C100 Series Operating Manual
-
11
-
3.3.4 Wiring terminal
3.3.4.1 Main Circuit Terminals
Description of main circuit terminals:
Symbol
Function
R
、
S
、
T
Power input:
220V class: 1- phase 200-240V50/60Hz
3- phase 200-240V50/60Hz
380V class: 3- phase 380-480V50/60Hz
Single phase connected to R
、
T
U
、
V
、
W
Power output, connect to the motor
-BR
、
+BR
Connect the brake resistor, make sure to set C02.10
、
C02.11 etc.
PE
Ground terminal