HLP-C100 Series
HLP-C100 Series Operating Manual
-
41
-
7.4 Parameter Group 03: Reference/Ramps
C03.03
Function Description
Range
Unit Default Setting
Maximum Reference 0.000~4999.000
50.000
C03.07
Function Description
Range
Unit Default Setting
Actual reference calculation
0~1
0
Function: Enter value for Maximum Reference.
Description of Choice: The sum of all internal and external references is
clamped (limited) to the maximum reference value.
Option: [0] Preset ref Reference source 1,2
[1] Preset reference priority
Description of Choice:
[0], Actual reference = Preset ref Reference source 1,2
[1], When using preset reference 1-N, actual reference = preset reference [1-N],
else actual reference = preset reference [0] + reference source 1,2
C03.0* Reference Limits
C03.10 Function Description
Range
Unit Default Setting
Preset Reference
-100.00~100.00[8] %
0.00
Function: This parameter is an array-8 to be used for presetting different
references.
Description of Choice: 100%= value set in C03.03; It contains 8 preset references
which are selectable via digital terminals or local bus. See C05.1*.
Selection of preset reference indicates with a three-digital binary
code. If the f requency converter detects the corresponding terminals
connected, then the bit is “1”, otherwise, the bit is “0”. Digital input
terminal
、
binary code and the corresponding relationship between pre-
set values as follows:
C03.1** References