HLP-C100 Series Operating Manual
HLP-C100 Series
-
28
-
Item
Parameter
No.
Function
Description
Setting range
Unit
Default
setting
Page
No.
Pa
ra
m
ete
r G
ro
up
0
6: A
na
lo
g I
n/O
ut
C06.13
Terminal VI
High current
0.01~20.00
mA
20.00
C06.14
Terminal VI
Low Ref./
Feedb.Value
-4999.000~4999.000
0.000
C06.15
Terminal VI
High Ref./
Feedb.Value
-4999.000~4999.000
50.000
C06.16
Terminal VI
Filter Time
Contant
0.01~10.00
s
0.01
C06.18
Terminal VI
Zero dead band
0.00~20.00
V/
mA
0.00
C06.19
Terminal VI
Mode
0: Votage mode;
1: Current mode;
0
C06.81
LCP Potmeter
Low Ref.
-4999.000~4999.000
0.000
C06.82
LCP Potmeter
High Ref.
-4999.000~4999.000
50.000
Pa
ra
m
ete
r G
ro
up
07
: PI
D
C
on
tro
l
C07.20
Process CL
Feedback
Resource
0: No Function;
1: Analog in VI;
11:Local bus;
0
C07.31
Process PI Anti
Windup
0:Disabled; 1:Enabled;
1
C07.33
Process PI
Proportional
Gain
0.0~10.00
0.01
C07.34
Process PI
Integral time
0.10~9999.00
s
9999.00
C07.38
Process PI Feed
Forward Factor
0~400
%
0
C07.39
On Reference
Bandwidth
0~200
%
5
C07.41
Process PI
Output Low
-100-100
%
0
C07.42
Process PI
Output High
-100-100
%
100