HLP-C100 Series Operating Manual
HLP-C100 Series
-
40
-
DC-brake current is applied to the motor.
C02.04 Function Description
Range
Unit
Default Setting
DC Brake Cut in Speed
0.0~400.0
Hz
0.0
Function: This parameter is for setting the DC brake cut in speed at which the
DC braking current (par.02.01) is to be actived, in connection with a
stop command. When set to 0 the f unction is off.
C02.10
Function Description
Range
Unit
Default Setting
Brake Function
0~2
0
Option: [0] off;
[1] Resistor brake, use the resistor brake to consume surplus energy
resulting f rom motor braking, and prevent the f requency converter to
trip due to over-voltage in the intermediate circuit;
Attention: Resistor brake is only f unctional when the f requency converter
build-in braking unit or external braking unit must be installed.
C02.11
Function Description
Range
Unit
Default Setting
Brake Resistor (ohm)
5~65535
Ω
*
Function: Set brake resistor value.
C02.17
Function Description
Range
Unit
Default Setting
Over-voltage Control
0~2
0
Option: [0] Disabled, The OVC is not active/required;
[2] Enabled, OVC is running;
Function: OVC is used to consume surplus energy by increasing the output
f requency. Select whether to enable OVC, which reduces the risk of
drive trip due to over voltage on the DC link caused by generative
power f rom load.
Attention: The OVC is not active/required if resistor brake has been chosen in
C02.10 (Brake Function).
C02.1* Brake Energy Funct.