HLP-C100 Series Operating Manual
HLP-C100 Series
-
60
-
Option: [0] Digital and control word , use both digital input and control word as
control;
[1] Digital only, use digital input as control;
[2] Control word only, use control word only as control;
7.9 Parameter Group 08: Comm. and Options
C08.01
Function Description
Range
Unit
Default Setting
Control mode
0~2
0
Option: [0] None, control word is inactive;
[1] FC RS485 , select local bus as control word source.
C08.02 Function Description
Range
Unit
Default Setting
Control Word Source
0~1
1
Option: [0] Off, No f unction;
[1] Freeze output, Freeze output until communication resumes.
[2] Stop, Stop with auto restart when communication resumes;
[3] Jogging, Run motor at jog f requency until communication resumes;
[4] Max. speed, Run motor at max.f requency until communication
resumes;
[5] Stop and trip, Stop motor and restart f requency in order to restart
via either LCP or Digital input .
Function: Select action to be taken in case of timeout.
C08.04 Function Description
Range Unit Default Setting
Contol Word Time Out Time
0~5
0
Function: This f unction is disabled, when the reference is set to 0. If the
reference is not set to 0, the control word timeout time is not exceeded,
and the serial communication is still innormal, action set in C08.04
will be carried out.
C08.03 Function Description
Range
Unit
Default Setting
Control Word Time
Out Time
0.1~6500.0
s
1.0
C08.0* Comm. General Settings