HLP-C100 Series Operating Manual
HLP-C100 Series
-
30
-
Item
Parameter
No.
Function
Description
Setting range
Unit
Default
setting
Page
No.
Pa
ra
m
ete
r G
ro
up
14
: S
pe
cia
l F
un
cti
on
s
C14.12
Function
at Mains
Imbalance
0: Trip; 1: Warning;
2: Disabled;
0
C14.20 Reset Mode
0: Manual reset;
1~10: Automatic reset
x 1~10; 11: Automatic
reset x 15;
12: Automatic reset
x 20; 13: In
fi
nite auto
reset;
0
C14.21
Automatic
Restart Time
0~600
s
10
C14.22
Operation
Mode
0: Normal Operation;
2: Initialisation;
3: Backup user
settings; 4: Recover
user settings;
0
C14.23 Trip Lock
0: Disable, Trip lock
fault reset do not
need power off
1: enable, Trip lock
fault reset need
power off
1
*C14.51
DC-Link
Voltage
Compensation
0: Off; 1: On;
0
Pa
ra
m
eter
G
ro
up
15
: Dr
iv
e I
nf
or
m
ati
on
C15.00
Operating Days 0~9999
d
C15.02
KWh Counter 0~65535
C15.03
Power up’s
0~2147483647
C15.06
Reset KWh
Counter
0: Do not reset;
1: Reset Counter;
C15.30
Fault Log: Error
Code
0~255
C15.31
Internal Fault
Reason
-32767~32767
C15.40
FC Type
View FC type
C15.41
Power Section
View power size of
the drive