HLP-C100 Series
HLP-C100 Series Operating Manual
-
57
-
Function: Enter the time constant, this is a
fi
rst-order digital low pass
fi
lter time
constant for suppressing electrical noise in analog input VI. A high
time constant value improves dampening but also increases the time
delay through the f ilter. This parameter can’t be adjusted while the
motor is running.
C06.16 Function Description
Range
Unit Default Setting
Terminal Filter Time Constant 0.01~10.00
s
0.01
Function: Set the dead-band of VI at 0 speed. When analog input VI ref.
low and ref. high have opposite signs, there must be a set point that
corresponding to an analogue value equals 0. In order to prevent the
set point jitter at zero point due to analog interference, this parameter
should be set properly.
Description of Choice: Point A as shown in the
fi
gure is the analog value that
corresponds to a setpoint that equals 0. It is calculated via analog low
、
high values and low
、
high references. U
AB
=U
AC
=C06.18/2
C06.18
Function Description
Range
Unit Default Setting
Terminal VI Zero Dead Band 0.00~20.00 V/mA
0.00
Option: [0] Voltage mode;
[1] Current mode;
Function: Select the input to be present on analog input VI.
C06.19
Function Description
Range
Unit
Default Setting
Terminal VI Mode
0~1
0
C06.8* LCP Potmeter
The LCP potmeter can be select either as reference resource or relative
reference resource.