HLP-C100 Series Operating Manual
HLP-C100 Series
-
56
-
Function: Enter VI High Voltage corresponding to Max. reference/feedback set
in C06.15.
C06.11
Function Description
Range
Unit Default Setting
Terminal VI High voltage 0.10~10.00
V
10.00
Function: Enter VI Low Current corresponding to Min. reference/feedback set
in C06.14.
C06.12
Function Description
Range
Unit Default Setting
Terminal VI Low Current 0.00~19.99 mA
mA
Function: Enter VI High Current corresponding to Max. reference/feedback
set in C06.15.
C06.13
Function Description
Range
Unit Default Setting
Terminal VI High Current 0.01~20.00 mA
20.00
Function: Enter VI Low Ref./Feedb. Corresponding to Min. voltage or min.
current set in C06.10 or C06.12.
C06.14 Function Description
Range
Unit Default Setting
Terminal VI Low
Ref. /Feedb.
-4999.000~4999.000
0.000
Function: Enter VI High Ref./Feedb. Corresponding to max voltage or max
current set in C06.11 or C06.13.
C06.15 Function Description
Range
Unit Default Setting
Terminal VI High
Ref. /Feedb.
-4999.000~4999.000
50.000