*C01.24 Function Description
Range
Unit Default Setting
Motor Current
Dep. motor data
A
*
Function: Enter motor current value f rom nameplate data.
Description of the choice: Factory settings depend on the unit size.
*C01.25 Function Description
Range
Unit
Default Setting
Motor Norminal Speed
100~9999
RPM
*
Function: Enter the motor nominal speed value f rom the nameplate data.
Description of the choice: Factory setting depends on the unit size.
Attention: If motor f requency has been changed in C01.23, Nominal Motor
Speed will be affected.
*C01.42 Function Description
Range
Unit
Default Setting
Motor Cable Length
0~150
m
5
Function: Enter the motor cable length connected between the motor and the
f requency converter.
Description of the choice: Set correct cable length can suppress noises resulted
f rom the motor.
C01.4* Motor Cable Length
C01.55
Function Description
Range
Unit
Default Setting
V/F Characteristic-V
0~999.9
V
0/Vn
Function: This parameter is an array parameter [0-5], used for setting voltage
[V0-V5] at each f requency point to manually form a V/F characteristic
matching motor. Frequency points are def ined in par. C01.56, V/F
characteristics - F.
Description of choice: This parameter is only f unctional when par. C01.01, Motor
Control Principle is set to V/F [0].
Attention: V0 factory setting is set to 0V, and U1-U5 factory setting is set to
Un (motor rated voltage).
C01.56
Function Description
Range
Unit
Default Setting
V/F Characteristic-F
0~400
Hz
0/Fn
Function: This parameter is an array parameter [0-5], used for setting
f requency points [F0-F5] to manually form a V/F characteristic
matching motor. Voltage at each point is def ined in par. C01.55, V/F