HLP-C100 Series
HLP-C100 Series Operating Manual
-
51
-
*C04.12 Function Description
Range
Unit
Default Setting
Motor Speed Low Limit
0.0~400.0
Hz
0.0
Function: Set the minimum limit for Motor Speed, the motor speed low limit
can be set to correspond to the minimum output f requency of the
motor shaf t . The motor speed low limit must not exceed the Motor
Speed High Limit in C04.14.
C03.95
Function Description
Range
Unit Default Setting
Ramp8 Ramp Down Time 0.10~300.00
S
*
Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
C03.96
Function Description
Range
Unit Default Setting
Link preset reference and 0.10~300.00
S
*
Option: [0] No link;
[1] Link.
Function: If choose [1] link preset reference and ramp time, preset reference
0-7 are corresponding to ramp time 1-8. For example, choose preset
reference 2 by using terminals control, the ramp time is 3.
7.5 Parameter Group 04: Limits/warnings
*C04.10 Function Description
Range
Unit
Default Setting
Motor Speed Direction
0~2
2
Option: [0] Clockwise, the motor shaf t rotates in clockwise direction; this setting
prevents the motor f rom running in counter clockwise direction.
[1] Counter clockwise, motor shaf t rotates in counter clockwise
direction, this setting prevents the motor f rom running in clockwise
direction.
[2] Both Directions, with this setting, the motor can run in both
directions.
C04.1* Motor Limits