HLP-C100 Series
HLP-C100 Series Operating Manual
-
53
-
C04.63 Function Description
Range
Unit
Default Setting
Bypass Speed to
0.0~400.0
Hz
0.0
Array: [3];
Function: This parameter is a dyadic array, [0] is used to set the bypass speed to
of bypass speed range 1, [1] is used to set the bypass speed to of bypass
speed range 2,and [2] is set as that of bypass speed range3.
*C04.58 Function Description
Range
Unit
Default Setting
Missing Motor Phase
Function
0~1
1
Option: [0] Off, f unctoin is disabled;
[1] On, f unction is enabled;
Attention: Missing motor phase causes motor torque to decrease. This f unction
may be disabled for special purpose (e.g. small motor running pure U/
f mode). However, choosing [0] Off, f unction disabled, may lead to
overheating, Holip strongly recommends to make an active setting to
avoid motor damage.
C04.61
Function Description
Range
Unit
Default Setting
Bypass Speed From
0.0~400.0
Hz
0.0
Array: [3]
Function: This parameter is a dyadic Array, [0] is used to set the bypass speed
f rom of bypass speed range 1, [1] is used to set the bypass speed f rom of
bypass speed range 2,and [2] is used to set that of bypass speed range3.
Description of Choice: Some systems call for avoiding some certain output
speed due to resonance problems in system. The drive will pass quickly
when it approaching to the Bypass Speed area.
C04.6* Speed Bypass