HLP-C100 Series
HLP-C100 Series Operating Manual
-
37
-
C01.71
Function Description
Range
Unit
Default Setting
Start Delay
0.0~10.0
S
0.0
Function: This parameter enables a delay of the starting time. The f requency
converter begins with the start f unction selected in par. 1-72. Set the
start delay time until acceleration is to begin.
Attention: Setting start delay to 0.0 sec. disables Start Function, [C01.72], when
start command is given.
C01.72
Function Description
Range
Unit
Default Setting
Start Function
0~2
2
Option: [0] DC Hold;
[2] Coast;
Function: Select [0], Motor is energized with DC holding current (par. C02.00)
C01.7* Start Adjustments
Characteristic - V.
Description of choice: This parameter is only f unctional when par. C01.01 Motor
Control Principle is set to V/F [0].
Attention: F0 factory setting is set to 0Hz, and F1-F5 factory setting is set to Fn
(Motor rated f requency); for par. C01.56 the following applies F0=0 and
F1
≤
F2
≤
F3
≤
F4
≤
F5.
Fig. 6.1 V/F characteristic diagram
Simplif y V/F characteristic by merging 2 or more points (voltages and
f requencies), which respectively are set equal.
The slope (ratio of V/F) af ter point (F5, V5) must be equal to the slope
between point (F5, V5) and the previous point.