HLP-C100 Series
HLP-C100 Series Operating Manual
-
7
-
Item
Speci
fi
cation
Display
8 segments, 5
numeric displays
Display f requency, warnings, status and
so on;
Indicator
Light FWD
、
REV
、
HZ
、
A
、
R/MIN
display various status of the inverter;
Data read-outs
Frequency setting, output f requency,
feedback value, output current, DC link
voltage, output voltage, output power,
input terminals state, output terminals
state, analogue input, 1-10 fault records
and accumulated working time etc.;
Accessory
Remote
mounting kit
Available when the control panel for
external use;
Copy card
Copy parameters f rom one inverter to
another ;
Environment
Enclosure
IP20;
Ambient
temperature
-10
℃
-40
℃
;
Humidity
5%-85% (95% without condensation) ;
Vibration test
1.14g;
Max. altitude
above sea level
1000m, derating use when more than
1000 meters;
Motor cable
length
Shield cable: 5 meters, unshield cable: 50
meters;
Attention: Inverter under special environment (derating) :
●
Derating for ambient temperature: If the f requency converter is
operated over 40
℃
ambient temperature, the continuous output current
should be decreased. The f requency converter has been designed
for operation at max 50
℃
ambient temperation with one motor size
smaller than normal. Continuous operation at f ull load at 50
℃
ambient
temperation will reduce the lifetime of the f requency converter.
●
Derating for low air pressure: The cooling capability of air is decreased
at low air pressure. Below 1000m altitude no de-rating is necessary but
above 1000m the ambient temperature or the maximum output current
should be decreased. Dcrease the output by 1% per 100m altitude above
1000m or reduce the max. ambient temperature by 1 degree per 200m.