Fault
Process Method
4. No fault
message or
screen display
Con
fi
rm whether the input f use meltdown;
Verif y whether control card is overload;
Suppose control card is overload, and 24V is shorted, please
remove the connection of control terminal;
Make sure if any fault message is displayed, and if no, please
contact Holip Company;
5. Motor can’t
rotate and
screen display
is normal
without fault
message
Press [Enter] on LCP;
Make sure whether the screen is active i.e. the screen display
can’t be switched or parameter can’t be edited;
Suppose screen is f reeze, please make sure screened cable
used and connected correctly;
If operation of the display screen is normal, please make
sure connection between motor and the f requency converter
is correct and then operate the drive in hand mode. Please
contact Holip Company if motor can’t rotate.