HLP-C100 Series
HLP-C100 Series Operating Manual
-
87
-
Receive data 2
Field
Description
01
FC address
10
Function
0C 1B
The register address of C03.10 is 310*10-1=3099 (0x0C1B)
00 01
The number of register
72 9E
CRC check
12.9 Exception code
When a communication exception is happened, the inverter returns data
format as following:
Address
Function
Exception code
CRC check
8 bits
8 bits
8 bits
16 bits
Exception code
Description
0x00
Parameter number does not exist
0x01 De
fi
ned parameters can not be written
0x02
The value exceeds the upper limit of the parameter
0x03 Index
does
not
exist
0x04 The
parameter
is
not
array
type
0x05 Data
type
exception
0x06 Only
use
for
reset
0x07 Cannot
be
changed
0x0B Not
allowed
to
write
0x11
Data cannot be changed in the current mode(some
parameter cannot be changed when the inverter is running)
0x12
Other exception
0x40
Invalid data address
0x41
Invalid length
0x42
Invalid length and value
0x43
Invalid parameter
0x82
The parameters has no bus connection
0x83
Factory settings, cannot be changed.