HLP-C100 Series
HLP-C100 Series Operating Manual
-
81
-
Coil address
0
1
46
Not in current limit
Current limit
47
No thermal warning
Thermal warning
Register
Description
00000-00007
Reserved
00008
Parameter index
00009-00989
Parameter group 00
00999-01989
Parameter group 01
01999-02989
Parameter group 02
…
…
15999-16989
Parameter group 16
The relationship between register address and parameter number is:
register address = parameter number × 10-1
12.3 Read Coil Status
Example: Detect inverter output f requency
Transmit: 01 01 00 30 00 10 3D C9 (Hexadecimal)
Receive: 01 01 02 00 20 B8 24 (Hexadecimal)
Transmit data
Field
Description
01
FC address
01
Funtion
00 30
Coil address (ADDRH ADDRL). 0x0030 convert to decimal
number is 48. Coil address 49 is f requency converter output
f requency.
00 10
Data bits number is 16. 0x 0010 convert to decimal number is 16
3D C9
CRC check
Receive data
Field
Description
01
FC address
01
Function
02
The read byte number is 2