HLP-C100 Series
HLP-C100 Series Operating Manual
-
47
-
C03.62
Function Description
Range
Unit Default Setting
Ramp3 Ramp Down Time 0.10~300.00
S
*
Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
C03.51
Function Description
Range
Unit Default Setting
Ramp2 Ramp up Time 0.10~300.00
s
*
Function: Enter the ramp-up time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.52 Function Description
Range
Unit Default Setting
Ramp2 Ramp down Time 0.10~300.00
S
*
Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
C03.60 Function Description
Range
Unit
Default Setting
Ramp3 Type
0~2
0
Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
C03.61
Function Description
Range
Unit Default Setting
Ramp3 Ramp up Time 0.10~300.00
S
*
Function: Enter the acceleration time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.6* Ramp3