HLP-C100 Series
HLP-C100 Series Operating Manual
-
43
-
C03.14
Function Description
Range
Unit Default Setting
Preset Relative
Reference
-100.00~100.00
%
0.00
Function: De
fi
ne an adjustable Preset Relative Reference which is to be added
to the total reference as a percentage value of the actual reference .
Total Reference=Actual ReActual Reference * Preset Relative
Ref Actual reference * Relative Scaling Reference
Example:
Min
Reference/
C03.02
Preset
Relative
Reference/
C03.14
Relative
Scaling
Reference
VI/C03.18=1
Preset
Reference/
C03.10
Max
Reference/
C03.03
Output
Frequency
(Hz)
0
0%
10V
20%
50
10+0+10=20
0
10%
8V
20%
50
10+1+8=19
0
20%
5V
20%
50
10+2+5=17
0
30%
3V
20%
50
10+3+3=16
0
40%
0V
20%
50
10+4+0=14
C03.15
Function Description
Range
Unit
Default Setting
Reference Resource1
0~21
1
C03.16
Function Description
Range
Unit
Default Setting
Reference Resource2
0~21
2
Option: [0] No f unction, no reference resource is de
fi
ned;
[1] Analog in VI, use signals f rom Analog input VI as reference
resource, see C06.1*;
[11] Local bus reference, use signals f rom Local bus reference as
reference resource, see C08.9;
[21] LCP potentiometer, use signals f rom LCP potentiometer as
reference resource, see C06.8*;
Function: C03.15
、
C03.16 de
fi
ne up to three different reference signals, the sum
of which de
fi
nes is the actual reference.