HLP-C100 Series Operating Manual
HLP-C100 Series
-
38
-
during start delay time; Select [2], Motor is coasted during start delay
time (inverter off ).
*C01.73 Function Description
Range
Unit
Default Setting
Flying Start
0~1
0
Option: [0] Disabled;
[1] Enabled;
Description of Choice: This f unction applies for the inertia load to restart due
to mains drop-out; If Clockwise[0] is selected(C04.10), and no rotating
motor is found, It is possible to use DC-brake command to ramp down
the motor speed to 0 rpm, and then start the motor in the normal way;
If Both directions [2](C04.10) is selected, and no rotating motor is found,
the drive will assume the motor is stationary or in low-speed rotation,
and then start the motor in the normal way. When Flying start is
enabled, C01.71 (Start delay) and C01.72 (Start f unction) is invalid.
Warning: This f unction is not suitable for hoisting applications.
C01.80
Function Description
Range
Unit
Default Setting
Function at Stop
0~1
0
Option: [0] Coast, the inverter is off;
[1] DC Hold, the motor is energized with a DC current. See par. C02.00
DC Hold Current for more information.
Function: Here it is possible to select the stop f unction according to different
applications.
C01.8* Stop Adjustments